MEDIUM VOLTAGE PRODUCTS
HT Switchgear: (3.3kV - 36kV)
The legendary Indoor Vertical Isolation VCB is a preferred product in various Utilities & Indian Railways. The vertical isolation & horizontal draw-out truck ensures more ground space & provides higher degree of compactness than horizontal isolation trucks. The product comes with high rigidity & best in class control solutions.
Technical DetailsThe KIOSK is specially designed for unmanned substations in the Outdoor distribution network. It is a standalone vacuum switchgear system with built in self-driven independent control supply for self-tripping & closing of CB. The product is well equipped for metering, control, protection & SCADA compatibility.
The product is available in two basic designsRoof bushing type with incoming & outgoing through roof bushings (Rated Voltage: 12 & 36 kV)
Line up type with incoming through bottom, rear / side cable entry & outgoing through bus bar / cables (Rated Voltage:12 kV)
It is a highly sought product in the utilities distribution segment. The product is specially designed for outdoor application with rated voltage of 12 kV to 36 kV. Over the years, the product has undergone a frequent design improvement that brings you a sense of satisfaction over reliability & safety
Technical DetailsRing Main Unit can also be provided with two number Load Break Switch with one number tee-off Vacuum Circuit Breaker with protective devices. It is highly flexible unit used in a wide range of applications including distribution switchboards, transformer substations, ring distribution networks and HV Connections to industrial & commercial sites. The units are developed to suit customer requirements for connection, supply, protection and sectionalizing with remote operation.
Circuit BreakerThe CB comprises of 3 vacuum interrupters, which have a fault-make, fault-break rating. Earthing of the outgoing cable is achieved by the use of CB in series with the off-load disconnector / selector switch.
Ring Switch Technical DetailsThese are fault-make load break switches utilizing a single break 3 position switches viz., ‘ON’, ‘OFF’ & ‘Earth’ functions.
USS is a prefabricated secondary substation with the combination of minimum voltage & switchgear, low voltage switchgear, Distribution Transformer and associated components of metering and protection, all fitted in one compact unit in accordance to the standards.
LOW VOLTAGE PRODUCTS
LV panels, MCC, PCC, APFC, VFD, SOFTSTARTER Panels & All types of Distribution boards
StandardsIEC-60439 Part 1&2, IS-8623 Part 1&2 with Customized design.
Fault levelUP TO 80kA with Al / Cu Bus bars
E-HOUSE
SI.NO | Name Of the Customer & Details |
---|---|
1. | South Bihar Power Distribution Company Limited | `
2. | Government of Odisha, Mega Lift Projects. |
4. | Hindustan Aeronautics Ltd. |
5. | TANTRANSCO |
7. | Neyveli Lignite Corporation Ltd |
9. | Government of India/Ministry of Defence CVRDE /Southern Railway CVRDE |
10. | National Mineral Development Corporation |
11. | Damodar Valley Corporation |
12. | KUIDFC – Karnataka Urban Infrastructure Development & Finance Corporation Ltd |
13. | KPTCL – Karnataka Power Transmission Corporation Limited |
Type of test | Product | IEC Clause | Rating |
---|---|---|---|
Short time withstand current and Peak withstand current test & Basic Short Circuit test duty-T100s | HT Panel with VCB-Indoor | IEC:62271-100(2008) | 12kV,630A,25kA,3Pole VCB with Panel |
Basic Short Circuit test Duties - T60,T30 & T10 | HT Panel with VCB-Indoor | IEC:62271-100(2008) | 12kV,630A,25kA,3Pole VCB with Panel |
Basic Short Circuit test Duty - T100a | HT Panel with VCB-Indoor | IEC:62271-100(2008) | 12kV,630A,25kA,3Pole VCB with Panel |
Basic Short Circuit test Duties - T60,T30 & T10 | HT Panel with VCB-Indoor | IEC:62271-100(2008) | 12kV,630A,25kA,3Pole VCB with Panel |
Single Phase Test | HT Panel with VCB-Indoor | IEC 62271-100 (2008) | 12kV,630A,25kA,3Pole VCB with Panel |
6 Cable Charging Current Switching Test Duty - CC1, Cable Charging Current Switching Test Duty - CC2 | HT Panel with VCB-Indoor | Clause 6.111.9 of IEC 62271-100 ed2.1, 2012 | 12kV,630A,25kA,3Pole VCB with Panel |
Temperature Rise Test - 1250A | HT Panel with VCB-Indoor | (Clause 6.5), IEC 62271-200 :2011 & IEC 62271-100 :2012 | 12kV, 1250A, 25kA, 3Pole VCB with Panel |
Mechanical Operation Test at ambient air temperature (M1 Class) | VCB Truck | Clause 6.101.2 of IEC 62271-100 ed2.1 (2012-09) | 12kV,1250A,25kA,3Pole VCB |
Lightning Impulse Voltage Test, Power Frequency Voltage Test | HT Panel with VCB-Indoor | (Clause-6.2.6.2), (Clause-6.2.6.1), IEC 62271-200 2011 | 12kV,1250A,25kA,3Pole VCB with Panel |
Ingress Protection - 54 | HT Panel with VCB | IEC 62271-200, Edition 2.0, 2011-10. i.e IP 54 Test Category 2, as per IEC 60529 Edition 2.2, 2013-08 Standard. Clause 11.5 and 13.4 | 12kV,1250A,25kA,3Pole VCB with Panel |
Internal Arc Fault test on cable chamber | HT Panel With VCB - Indoor | (Clause - 6.106) IEC 62271-200, 2011 | 12kV, 1250A, 26.3kA, Indoor VCB Panel |
Internal Arc Fault test on Busbar chamber. | HT Panel With VCB - Indoor | (Clause - 6.106) IEC 62271-200, 2011 | 12kV, 1250A, 26.3kA, Indoor VCB Panel |
Internal Arc Fault test on Breaker Chamber | HT Panel With VCB - Indoor | (Clause - 6.106) IEC 62271-200, 2011 | 12kV, 1250A, 26.3kA, Indoor VCB Panel |
Short time withstand current and peak withstand current tests | HT Panel With VCB - Indoor | (clause - 6.6), IEC : 62271-200: 2011 | 12kV, 1250A, Indoor VCB Panel |
Short time withstand current and peak withstand current test on main circuit | HT Panel With VCB - Indoor | Sub Clause - 6.6a, IEC - 62271-200: 2011 26.3kA rms for 3.0 s & 65.75kA Peak on main circuit | 36kV, 1250A Indoor VCB Panel |
Basic Short Circuit test duties - T100s | HT Panel with VCB - Indoor | Clause 6.106.4 of IEC 62271-100,2008 with Amendment 1 of 2012.Amendment 2 of 2017 | 12kV,1250A,25kA, 3pole Indoor VCB with panel |
Capacitor bank current switching tests, test duty -1 (BC1) & test duty -2(BC2) (C1 Class) | HT Panel with VCB - Indoor | Clause 6.111.9.2.2 of IEC 62271-100,2008 with Amendment 1 of 2012.Amendment 2 of 2017 | 12kV,1250A,25kA, 3pole Indoor VCB with panel |
Temperature rise test - 800 Amps (Aluminium Busbar - 80 x 10mm) | HT Panel with VCB - Indoor | IEC 62271 - 200: 2011 & IEC 62271 - 1:2017 | 6.6kV,800A,26.3kA VCB panel |
Temperature rise test - 630 Amps (Copper Busbar - 40 x 10mm) | HT Panel with VCB - Indoor | IEC 62271 - 200: 2011 | 36kV,630A,26.3kA Indoor VCB panel |
Short time withstand current and peak withstand current test on main circuit | HT Panel With VCB - Indoor | Sub Clause - 6.6a, IEC - 62271-200: 2003 | 12kV 630A VCB panel |
Temperature rise test - 2000A(Copper Busbar - 60x12mm) | HT Panel Without VCB – Indoor | As per customer's instructions | 11kV, 2000 A HT PANEL |
Temperature rise test (Copper Busbar - 50x10mm) | HT Panel With VCB - Indoor | IEC 62271 - 200: 2011 | 33kV 1250A HT PANEL |
Ingress Protection - 54 | LT Panel - Indoor / Outdoor (PDB Panel) | IP 54 Test as per IS/IEC 60947-1:2007 Standard. Clause C 13.4 i.e IP 54 Category 2 test as per IS/IEC 60529, Edition 2.1, 2001-02 standard. Clause 13.4. | IP54 |
Ingress Protection - 55 | LT Panel - Indoor / Outdoor (PDB Panel) | IP 55 Test as per IS/IEC 60947-1:2007 Standard. Clause C 13.4 i.e IP 55 Category 2 test as per IS/IEC 60529, Edition 2.1, 2001-02 standard. Clause 13.4. | IP55 |
Short Circuit Withstand Test | LT Panel - Indoor | Sub-clause 8.2.3 of IS 8623 (Part 1):1993/IEC Pub 493-1 (1985) (Reaffirmed 2004) | RMS : 80kA/1Sec, Peak : 176kA/1Sec,6000A,415VAC |
Temperature Rise Test | LT Panel - Indoor | IS:8623-Part 1-1993/IEC:60439-Part 1-1985 | 6000A,415VAC |
Short Circuit Withstand Test | NSP LT Bus duct Indoor | Sub-clause 10.11.5.3.3 &10.11.5.3.5 of IEC 61439-1:2011 & IEC 61439-6:2012 | RMS : 50kA/1Sec, Peak : 105kA/1Sec,2000A,415VAC |
Temperature Rise Test | NSP LT Bus duct Indoor | IEC 61439 Part 6-2012 | 2000A,415VAC |
Ingress Protection - 42 | LT Panel - Indoor | IEC 60529 Edition 2.2, 2013-08 standard Clause 13.2 and 14.2.2. | IP42 |
Temperature Rise Test | LT DC Distribution Board Panel | IEC 61439-2:2011 | 200 A, 220V |
Short Circuit Withstand Test | LT AC Distribution Board Panel | Clause no : 10.11 of IEC 61439-2:2012 | 200 A,415V |
Ingress Protection - 52 | Indoor DC Lighting Panel - 6 Way | IEC :60529 Category II | IP52 |
Lightning Impulse Voltage Test | HT Panel With VCB - Indoor | (Clause - 6.2) IEC 62271-200/2011-10. | 36kV 1250A HT PANEL |
Internal Arc Fault test on cable chamber | HT Panel With VCB - Indoor | (Clause - 6.106) IEC 62271-200, 2011 | 36kV, 1250A, 25kA, Indoor VCB Panel |
Internal Arc Fault test on Busbar chamber. | HT Panel With VCB - Indoor | (Clause - 6.106) IEC 62271-200, 2011 | 36kV, 1250A, 25kA, Indoor VCB Panel |
Internal Arc Fault test on Breaker Chamber | HT Panel With VCB - Indoor | (Clause - 6.106) IEC 62271-200, 2011 | 36kV, 1250A, 25kA, Indoor VCB Panel |